A.N.B. Electronics Co., Ltd. · Industrial power solutions in Thailand
Product resource · Engineering reference

MEAN WELL LRS-200-48

48V DC · 4.4A · 211.2W enclosed AC/DC power supply

Single-output enclosed switching supply in the MEAN WELL LRS-200 series. Use the verified ratings below to assess load compatibility and compare the available output-voltage variants.

Before specifying, verify the latest model ratings, datasheet revision, applicable approvals, availability, and installation derating requirements using the manufacturer datasheet linked below.

MEAN WELL LRS-200 power supply

Specifications that matter

211.2W
Rated output power

Model electrical ratings

Output voltage48V
Rated output current4.4A
Rated output power211.2W
Typical efficiency90%
Output adjustment43.2 ~ 52.8V
Ripple & noise (maximum)200mVp-p

Engineering considerations

Verify AC input conditions, load profile, installation orientation, wiring, ventilation and ambient-temperature derating against the manufacturer's datasheet.

Nominal series power is not necessarily the rated power of every output-voltage variant. This page uses the model-specific rating.

Source: Manufacturer Datasheet.

Will LRS-200-48 support your load?

Estimate steady-state load utilization at the model's nominal DC output. This is a planning calculation, not a substitute for temperature derating, startup-current or transient-load analysis.

Compare LRS-200 models

Voltage variants within this series differ in output current, rated power and efficiency. Select the model matching your load voltage first.

ModelDC outputRated currentRated powerEfficiency (typ.)
LRS-200-3.33.3V40A132W83%
LRS-200-4.24.2V40A168W86%
LRS-200-55V40A200W87%
LRS-200-1212V17A204W87.5%
LRS-200-1515V14A210W88%
LRS-200-2424V8.8A211.2W89.5%
LRS-200-3636V5.9A212.4W89.5%
LRS-200-4848V4.4A211.2W90%

Explore the complete LRS family →

Installation considerations

Thermal design

Apply the manufacturer's temperature and input-voltage derating curves; ensure adequate free-air convection and clearance.

Load characteristics

Check startup surges, motor loads, capacitive loads and transient peaks in addition to steady-state current.

Electrical safety

Use qualified installation practices, correct protective earth and appropriate input/output wiring. Verify the latest approvals for your application.

Manufacturer resources & quotation