Manufacturer specifications
| Function | DIN-rail DC-UPS module |
|---|---|
| Continuous current | 20 A |
| System voltage | 24 V DC nominal |
| Operating voltage range | 24–29 V DC input; 21–29 V DC output |
| Current capability | 20 A continuous discharge |
| Operating temperature | −30 to +70 °C (consult derating curve) |
| DIN-rail width | 40 mm |
| Engineering features | External 24 V lead-acid battery (two 12 V batteries in series or one 24 V battery); 4–135 Ah supported battery capacities; 2 A battery charging; DC bus, battery-failure and discharge status indication. |
Engineering selection checklist
- Confirm a regulated 24 V DC supply, 24 V battery pack, and load current.
- Estimate backup runtime from battery usable capacity and actual discharge load; battery condition and temperature affect runtime.
- Confirm external battery fuse, conductor sizing, charging requirements, and low-voltage cutoff behavior.
Check installation wiring, protective devices, and temperature-dependent ratings against the manufacturer datasheet before finalizing a system.
Compare DUPS modules
| Model | Continuous current | DIN-rail width |
|---|---|---|
| DUPS20 | 20 A | 40 mm |
| DUPS40 | 40 A | 63 mm |
Technical resources
Refer to the manufacturer document for complete ratings, wiring diagrams, derating curves, and safety instructions.
Manufacturer DatasheetDiscuss this model with ANB →