Manufacturer specifications
| Function | DIN-rail redundancy module |
|---|---|
| Continuous current | 20 A |
| System voltage | 12 / 24 / 48 V DC (variant-dependent) |
| Operating voltage range | 9–14 V / 19–29 V / 36–60 V DC |
| Current capability | 30 A for 5 seconds |
| Operating temperature | −40 to +80 °C (derating above +60 °C) |
| DIN-rail width | 32 mm |
| Engineering features | Two input channels and one output; 1+1 and N+1 redundant supply arrangements; MOSFET-based low-drop path; two DC OK monitoring channels. |
Engineering selection checklist
- Match the supply nominal voltage and the specific 12 V, 24 V, or 48 V DRDN variant.
- Confirm total continuous load current, branch supply current, and redundancy topology.
- Check maximum voltage drop, conductor sizing, DC OK relay signaling, and temperature derating.
Check installation wiring, protective devices, and temperature-dependent ratings against the manufacturer datasheet before finalizing a system.
Compare DRDN modules
| Model | Continuous current | DIN-rail width |
|---|---|---|
| DRDN20 | 20 A | 32 mm |
| DRDN40 | 40 A | 55 mm |
Technical resources
Refer to the manufacturer document for complete ratings, wiring diagrams, derating curves, and safety instructions.
Manufacturer DatasheetDiscuss this model with ANB →